Hello,
I’m trying to shop around for a possible extension cord for this 250v, 50amp outlet.
We’d be trying to use an electric dryer from this, but would preferably have it extend nearer a window on the other side of a garage (~25-30 ft, generous measurement). We’d likely pick up an older, used, basic dryer model, and not sure what those electrical needs will specifically be, but trying to plan ahead in case something needs to be altered.
This is the closest I’ve found which might work:
Most other cords with 3 prongs had them sort of curved/circular. Yet, this says only 30 amps.
Is there different or specific wording which might assist my search? Or would something like the above cord work for our situation?
Thank you for taking the time to read my post. I appreciate any advice or directions.
Extension cords are not for permanent use. It will void any insurance claims, and having the dryer 25 feet from the outlet just screens permanent use to an adjustor or inspector.
Even if you find one do not use it. What you have found so far is a guarantee of a fire.
Get an actual sparky to run some conduit on the wall of the garage and move the outlet. It’s probably the cheapest option on the table.
But I’m wondering why you want to move the dryer closer to the window and what the dryer vent situation is. There might be a different solution to your problem.